XTV1272 battery is specially designed for extreme temperatures (-20 to 50 ℃). Innovative Valve egulated Lead-Acid (VRLA) technology enables a 12-year design life in standby use, or more than 260 cycles at 100% discharge.
CSB Batteries can be stored for more than 6 months at 25°C (77°F) Please charge batteries before using. For higher temperatures the time interval will be shorter.
Terminal
F2-Faston Tab 250
Container Material
ABS(UL 94-HB/File E50263)*Flammability resistance of (UL 94-V0/File E88637) can be available upon request.
Dimensiones
Caracteristicas de Corriente de Descarga Constante Unidad:Amperios (25°C,77°F)
Tension Final/Tiempo
5MIN
10MIN
15MIN
30MIN
1HR
2HR
3HR
4HR
5HR
8HR
10HR
20HR
1.60V
27.67
17.69
13.38
7.94
4.60
2.67
1.93
1.52
1.25
0.88
0.71
0.38
1.67V
26.84
17.37
13.27
7.87
4.47
2.63
1.89
1.50
1.24
0.87
0.70
0.38
1.70V
25.77
17.07
13.15
7.81
4.41
2.61
1.89
1.49
1.23
0.86
0.70
0.38
1.75V
24.61
16.41
12.93
7.74
4.31
2.60
1.88
1.47
1.22
0.84
0.69
0.37
1.80V
21.81
15.36
12.30
7.52
4.22
2.57
1.86
1.47
1.21
0.82
0.68
0.37
1.85V
18.33
13.90
11.23
7.10
4.10
2.48
1.79
1.42
1.19
0.80
0.66
0.36
Caracteristicas de Corriente de Descarga Constante Unidad:Watts (25°C,77°F)